Marine water cooled water chiller

Brief Description

Product Description

Marine water cooled water chiller

Feature



Technical Data
MWWL Sea water cooled screw chiller unit parameter
Model
Parameter
160S 210S 280S 320S 400S 540S 600S 720S 810S 920S 800D 1080D 1200D 1440D 1620D 1840D
Cooling Capacity 50HZ KW
60HZ
Throttling Methods Liquid crystal/Touch automatic computer control/Thermal expansion valve/Electronic expansion valve
Refrigerant R22/R407c
Refrigerant Charge Kg 25 30 40 51 65 71 79 90 98 123 65×2 71×2 79×2 90×2 98×2 123×2
Compressor Input power 50HZ KW 42 55 72 83 100 126 141 165 187 980 200 525 282 330 374 412
60HZ 50 67 87 94 122 153 170 199 226 250 244 306 340 398 452 500
Type 5+6 Asymmetric semi-hermetic two-screw
Evaporator Model Efficient dry shell and tube(1.65Mpa water Pressure)
Water Flow 50HZ m3/h 28 37 49 55 69 93 103 125 140 159 138 186 206 250 280 318
60HZ 33 45 59 64 85 112 126 150 168 190 169 224 252 300 336 338
Water resistance KPa 48 48 49 50 53 55 60 60 63 66 68 65 65 68 68 68
Inlet and outlet Diameter mm DN80 DN100 DN125 DN150 DN200 DN250
Condenser Model Efficient shell and tube(1.65Mpa water Pressure)
Water Flow 50HZ m3/h 35 47 62 69 87 117 129 158 175 199 173 234 258 316 350 398
60HZ 42 56 74 80 106 140 158 188 210 238 212 280 280 376 420 476
Water resistance KPa 42 42 46 46 48 52 54 56 58 67 67 42 42 46 46 48
Inlet and outlet Diameter mm DN80 DN100 DN125 DN150 DN125×2 DN150×2
Dimension Length mm 2200 2400 2800 2900 3200 3500 3500 4000 4200 4550 3300 3500 3600 4000 4300 4600
Width 1100 1100 1250 1250 1400 1400 1400 1600 1600 1800 1800 1800 1800 1800 1900 1900
Height 1500 1500 1600 1600 1600 1800 1800 1800 2000 2000 2100 2100 2200 2200 2300 2300
Unit Weight Kg 1050 1200 1250 1480 1990 2000 2100 2900 3450 3650 3800 4050 4400 4950 5480 5990
Operation Weight Kg 1170 1350 1400 1750 2200 2250 2390 3200 3770 3970 4150 4200 4650 5200 5650 6100
Note:
1.Cooling capacity nominal conditions:.Chilled water inlet temperature:12,Chilled water outlet temperature: 7,.Cooling water inlet temperature:32, outlet temperature: 37;Fouling factor:0.086m2/KW.
2.Allowable voltage fluctuation:±10%
Allow phase voltage difference±2%.

Application
It is widely used in all kinds of passenger ships, cargo ships, warships and offshore oil platfroms

Product Tags